Onsite production of medical air: is purity a problem?

verfasst von: Paul Edwards, Patricia-Ann Therriault, Ira Katz

Erschienen in: Multidisciplinary Respiratory Medicine | Ausgabe 1/2018

Abstract

Introduction

Medical air (MA) is widely used in hospitals, often manufactured onsite by compressing external ambient air and supplied through a local network piping system. Onsite production gives rise to a risk of impurities that are governed by the same pharmacopoeia purity standards applicable to commercially produced MA. The question to be addressed in this paper is how to assess if a lack of purity poses a medical problem?

Methods

The MA produced onsite at a major Canadian hospital was monitored for carbon dioxide (CO2) and other impurity gases at high frequency (one per minute) over a two-month period.

Results

The average CO2 concentration was 255 ppm. The United States Pharmacopeia (USP) threshold of 500 ppm was exceeded during 1% of the total study period, and the average while exceeding the threshold was 526 ppm. The maximum concentration was 634 ppm.

Discussion and conclusion

To our knowledge, there is only one study that evaluated the effects suffered by respiratory patients of elevated nitric oxide in MA; thus, it is not clear what are the medical bases for the thresholds stated in the USP. To perform a Quality Risk Assessment, the threshold and the time above threshold should be considered in determining the frequency of sampling and analysis, and operating methods required to ensure the quality of MA entering the pipeline meets the clinical, regulatory, and patient safety standards. In conclusion, because the USP does not provide impurity thresholds for specific patients nor time above thresholds, there is a need for the medical community to determine these quantities before it can be known if the purity of MA is a problem.

Introduction

Medical air (MA) is widely used for aerosol drug delivery, high flow therapy, mechanical ventilation, neonatal environment control, infant resuscitation, general anesthesia, and hyperbaric therapy. MA can be produced by external manufacturers, filled in cylinders and transported to the site of use. This form of supply is directly regulated by the relevant country’s pharmacopeia [1]. However, for hospitals MA is most efficiently manufactured onsite by compressing external ambient air and supplied through a local network piping system. Onsite production gives rise to a risk of impurities that are governed by the same pharmacopoeia purity standards, and should be assessed by the facility’s staff [2]. The sources of impurities can be categorized as systemic or extrinsic; where the systemic sources arise due to the manufacturing and distribution systems themselves and extrinsic sources arise from the external air input. Furthermore, the extrinsic sources are either endemic (i.e., local to the production site) or ambient (arising from the pollution levels in the environment).
In brief, onsite MA production consists of outside air being drawn into the system by a compressor, through particulate filters. The MA passes through a dryer before entering the distribution network. There also must be a backup supply based on cylinders. Note that there would usually be multiple components such as compressors and dryers to optimize production and to account for normal downtime. Of particular importance are dryers that consist of dual columns that operate on the principle of pressure swing adsorption, when one column swings to low pressure to dehumidify the absorbing material and the second takes over as the active dryer.
For context, the United States Pharmacopeia (USP) threshold values for MA are: oxygen < 19.5% v/v and > 23.5% v/v, carbon monoxide > 10 ppm, carbon dioxide > 500 ppm, nitrous oxide + nitric oxide > 2.5 ppm, sulphur dioxide > 5 ppm, and humidity <− 5 °C pressure dew point [3].
The question to be addressed in this paper is how to assess the purity of onsite produced MA and if a lack of purity poses a medical problem. That is, what are the elements of a Quality Risk Assessment for onsite produced MA that should be understood and addressed by the medical community. We take advantage of a unique sample dataset; high frequency measurements (one per minute) over a two-month period of carbon dioxide (CO2) to frame the discussion.

Methods

The MA produced onsite at a major Canadian hospital (the name of the hospital cannot be revealed for contractual reasons) was monitored using an AerAlin device (Vitalaire, Mississauga, Canada) that monitors the oxygen content and contaminant levels. Using seven independent sensors the AerAlin can monitor the following USP designated components: oxygen, carbon dioxide, carbon monoxide (CO), dewpoint (to determine humidity), nitric oxide and nitrogen dioxide together (NOx), and sulphur dioxide (SO2). In this short paper we only report in detail on CO2 results. The internal CO2 sensor (Vaisala CARBOCAP series GMT220, Helsinki, Finland) has an accuracy: ± (1.5% of range + 2% of reading). This sensor has been used in a wide variety of scientific and industrial activities [46]. Measurements were recorded at a frequency of 1/min, from July 28th to September 12th, 2017.

Results

Figure 1 shows the time history of CO2 concentration during the study period. The red horizontal line is the USP threshold. The average CO2 concentration was 255 ppm. The USP threshold of 500 ppm was exceeded during 1% of the total study period (719 measurements), and the average while exceeding the threshold was 526 ppm. The maximum concentration was 634 ppm.
Considering the other USP criteria; there were nine threshold breaches of NOx (maximum 2.7 ppm) with an overall average of 0.03 ppm. There were no threshold breaches for the other USP criteria: O2 (avg 21.0%, max 21.1%, min 20.9%), CO (avg 1.7 ppm, max 9.6 ppm), dew point (avg − 42.1 °C, max 8.3 °C), and SO2 (avg < 0.001 ppm, max 0.1 ppm).

Discussion and conclusion

In this paper a dataset of CO2 concentration measurements in onsite produced MA indicates periodic breaches in the USP threshold. To our knowledge, this is the first example of testing of onsite production of MA to appear in the peer reviewed literature.
The reason for the breaches in CO2 threshold are attributed by us to the dryer, which captures CO2 concomitant to humidity. When it is almost saturated with humidity, before the swing to purge mode, previously captured CO2 is released into the airstream at higher concentrations than in the original supply. Thus, this is considered a systematic impurity source.
We believe this example of CO2 concentration presented herein showing periodic systematic impurity breaches is representative of potential extrinsic impurity problems, though during the measurement period at this site there were only the nine other threshold breaches of NOx (maximum 2.7 ppm).
While there are numerous studies confirming the health effects of common air pollutants [7], to our knowledge there is only one study that evaluated the effects suffered by respiratory patients inhaling contaminated MA. This study showed that unintended inhalation of NO in industrialized areas may alter the PaO2 and may make the therapeutic use of NO less successful [8]. Another study concluded that low levels of carboxyhemoglobin (due to breathing CO) exacerbate myocardial ischemia during graded exercise in subjects with coronary artery disease [9]. Thus, overall it is not clear what are the medical bases for the thresholds stated in the USP.
To perform a Quality Risk Assessment, the threshold and the time above threshold should be considered in determining the frequency of sampling and analysis, and operating methods required to ensure the quality of MA entering the pipeline meets the clinical, regulatory, and patient safety standards. In the greater context of MA provided in cylinders, recalls have been made for levels of 720 PPM [10].
In conclusion, because the USP does not provide impurity thresholds for specific patients nor time above thresholds, there is a need for the medical community to determine these quantities before it can be known if the purity of MA is a problem.

Availability of data and materials

Upon request
Not applicable

Competing interests

Vitalaire, Canada is a provider of medical air systems and monitoring services. PE and PAT works in Vitalaire-Canada, whereas IK is part of Medical R&D of Air Liquide Santé International.

Publisher’s Note

Springer Nature remains neutral with regard to jurisdictional claims in published maps and institutional affiliations.
Open AccessThis article is distributed under the terms of the Creative Commons Attribution 4.0 International License (http://​creativecommons.​org/​licenses/​by/​4.​0/​), which permits unrestricted use, distribution, and reproduction in any medium, provided you give appropriate credit to the original author(s) and the source, provide a link to the Creative Commons license, and indicate if changes were made. The Creative Commons Public Domain Dedication waiver (http://​creativecommons.​org/​publicdomain/​zero/​1.​0/​) applies to the data made available in this article, unless otherwise stated.
Literatur
4.
Zurück zum Zitat De Godos I, Mendoza JL, Acién FG, Molina E, Banks CJ, Heaven S, et al. Evaluation of carbon dioxide mass transfer in raceway reactors for microalgae culture using flue gases. Bioresour Technol. 2014;153:307–14.CrossRefPubMed De Godos I, Mendoza JL, Acién FG, Molina E, Banks CJ, Heaven S, et al. Evaluation of carbon dioxide mass transfer in raceway reactors for microalgae culture using flue gases. Bioresour Technol. 2014;153:307–14.CrossRefPubMed
5.
Zurück zum Zitat Messerli J, Bertrand A, Bourassa J, Bélanger G, Castonguay Y, Tremblay G, et al. Performance of low-cost open-top chambers to study long-term effects of carbon dioxide and climate under field conditions. Agron J. 2015;107:916–20.CrossRef Messerli J, Bertrand A, Bourassa J, Bélanger G, Castonguay Y, Tremblay G, et al. Performance of low-cost open-top chambers to study long-term effects of carbon dioxide and climate under field conditions. Agron J. 2015;107:916–20.CrossRef
6.
Zurück zum Zitat Tsalaporta E, Brady N, MacElroy JMD. Experimental and modelling studies of CO2/N2 mixture separations using amine functionalised silicas. Adsorption. 2017;23:847–69.CrossRef Tsalaporta E, Brady N, MacElroy JMD. Experimental and modelling studies of CO2/N2 mixture separations using amine functionalised silicas. Adsorption. 2017;23:847–69.CrossRef
Metadaten
Titel
Onsite production of medical air: is purity a problem?
verfasst von
Paul Edwards
Patricia-Ann Therriault
Ira Katz
Publikationsdatum
01.12.2018
Verlag
BioMed Central
Erschienen in
Multidisciplinary Respiratory Medicine / Ausgabe 1/2018
Elektronische ISSN: 2049-6958
DOI
https://doi.org/10.1186/s40248-018-0125-8

Weitere Artikel der Ausgabe 1/2018

Multidisciplinary Respiratory Medicine 1/2018 Zur Ausgabe

Leitlinien kompakt für die Innere Medizin

Mit medbee Pocketcards sicher entscheiden.

Seit 2022 gehört die medbee GmbH zum Springer Medizin Verlag

Update Innere Medizin

Bestellen Sie unseren Fach-Newsletter und bleiben Sie gut informiert.